Existing system
- Chillers
- 2 YORK units selected for replacement; COP approximately 3.0
- Chilled-water pumps
- No VFD
- Annual plant electricity
- Approximately 2,552,000 kWh/year

Manufacturing retrofit
A turnkey chiller plant modernization delivered while the Dong Nai factory remained in production.
Results
Project story
The challenge
The plant’s existing YORK chillers operated at approximately COP 3.0. Chilled-water pumps had no VFD, and the reference records approximately 2,552,000 kWh/year of chiller plant electricity use. APC had to replace two YORK chillers without interrupting production.
Our solution
APC supplied a 520 RT SMARDT oil-free magnetic-bearing chiller with four compressors, iCPECS control of the chilled-water pumps, condenser-water pumps and cooling towers, pump VFDs, piping and field instruments.
The result
The reference reports approximately 3,100 kWh/day and 1,131,500 kWh/year of energy savings, with roughly 50% chiller savings against the previous system. Maintenance costs were reduced and selected removed components were retained as spares.
Before & after
Scope of supply
18 Oct – 20 Dec 2015
Key equipment
520 RT, approximately 1,828 kWr; 4 compressors
View equipmentChilled-water pumps, condenser-water pumps and cooling towers
Piping, power connections and measurement points
Commissioning data
The following part-load ranges describe this installation’s commissioning tests. They are not rated performance guarantees for other projects.
| Load | Capacity (kWr) | Input (kWe) | COP |
|---|---|---|---|
| 59–63% load | 920–995 | 120–133 | 7.4–8.0 |
| 43–45% load | 680–717 | 74–79 | 8.7–9.6 |